Calculation of Fault Current Using Impedance Diagram

Let us first illustrate the calculation of the fault current using the impedance diagram with the help of the following examples.

Example
Consider the power system of Fig. 6.8 in which a synchronous generator supplies a synchronous motor. The motor is operating at rated voltage and rated MVA while drawing a load current at a power factor of 0.9 (lagging) when a three phase symmetrical short circuit occurs at its terminals. We shall calculate the fault current that flow from both the generator and the motor.
We shall choose a base of 50 MVA, 20 kV in the circuit of the generator. Then the motor synchronous reactance is given by
  per unit  
Also the base impedance in the circuit of the transmission line is
  Ω  




Fig. 1  generator supplying a motor load though a transmission line.

Therefore the impedance of the transmission line is
  per unit  
The impedance diagram for the circuit is shown in Fig. 6.9 in which the switch S indicates the fault. 




Fig. 2  Impedance diagram of the circuit of Fig. 6.8.
The motor draws a load current at rated voltage and rated MVA with 0.9 lagging power factor. Therefore
  per unit  
Then the subtransient voltages of the motor and the generator are
  per unit
 per unit
 
Hence the subtransient fault currents fed by the motor and the generator are
  per unit
 per unit
 
and the total current flowing to the fault is
  per unit
 
Note that the base current in the circuit of the motor is
  A
 
Therefore while the load current was 1603.8 A, the fault current is 7124.7 A.